sensor switch WSRA Series Wall Switch Sensor with Occupancy

Manylebau:
- Series: WSRA Series
- Operational Settings: Occupancy Time Delay, On Mode, Switch
- Modes, Darkness Set-Point, Photocell Mode, LED Operation, Manual On
- Grace Period, Predictive Exit Time, Predictive Grace Time, Fade On Rate
Occupancy Time Delay:
The occupancy sensor can be set to keep the lights on for different durations after detecting occupancy. Adjust the setting as per your preference.
Ar Modd:
Choose between Automatic On, Manual On, or Reduced Turn-On modes based on your requirements. Automatic On turns the lights on automatically upon occupancy detection, Manual On requires manual intervention to turn the lights on, and Reduced Turn-On initially ignores small motions.
Moddau Newid:
Switch between different modes such as Switch Disable, Predictive Mode, and Predictive Mode with Expiration. These modes control how the sensor operates after a certain period of inactivity.
Darkness Set-Point / Inhibit Set-Point:
Set the ambient light level at which the lights will be adjusted to the High Trim setting. The Set Now option automatically selects the Darkness Set-Point based on current conditions in the room.
Modd Ffotogell
Enable or disable the feature that prevents lights from turning on when the light level is above the Inhibit Set-Point.
Adfer Rhagosodiadau
Reset all functions to their original settings if needed.
Gweithrediad LED
Select the behavior of the device’s LED indicator.
Manual On Grace Period
Set a grace period for manual control of the lights when in Manual On mode.
Predictive Exit Time and Predictive Grace Time
Adjust the time intervals for predictive exit and grace periods when occupants leave the room.
Fade On Rate
Set the time required for the lights to reach their preset brightness level.
Operational settings
Occupancy Time Delay:
Am faint o amser y bydd synhwyrydd deiliadaeth yn cadw'r goleuadau ymlaen ar ôl iddo ganfod deiliadaeth ddiwethaf.
| Gosodiad | Oedi Amser Meddiannaeth |
|---|---|
| 1 | 30 eiliad |
| 2 | 2.5 mun |
| 3 | 5.0 mun |
| 4 | 7.5 mun |
| 5 | 10.0 mun (diofyn) |
| 6 | 12.5 mun |
| 7 | 15.0 mun |
| 8 | 17.5 mun |
| 9 | 20.0 mun |
| 10 | 22.5 mun |
| 11 | 25.0 mun |
| 12 | 27.5 mun |
| 13 | 30.0 mun |
3=On Mode
Ddim yn berthnasol gyda'r Opsiwn Swydd Wag (VA).
Awtomatig Ymlaen
Mae'r synhwyrydd yn troi'r goleuadau ymlaen yn awtomatig pan fydd yn canfod deiliadaeth.
Llawlyfr Ymlaen
Mae angen i'r synhwyrydd wasgu'r botwm i droi'r goleuadau ymlaen.
Llai o Droi Ymlaen
Mae'r synhwyrydd ar fin canfod symudiadau mawr yn unig, gan anwybyddu i bob pwrpas unrhyw signalau Isgoch Goddefol (PIR) a adlewyrchir. Bydd preswylwyr yn dal i gael eu canfod ar unwaith pan fyddant yn mynd i mewn i'r ystafell gan fod eu signal PIR yn fawr. Unwaith y bydd y goleuadau ymlaen, mae'r synhwyrydd yn dychwelyd i'r sensitifrwydd mwyaf.
- Awtomatig Ymlaen
- Llai o Droi Ymlaen
- Manual On ‘
4=Switch Modes
Ddim yn berthnasol gyda'r Opsiwn Swydd Wag (VA).
Newid Galluogi (Diystyru i ffwrdd)
Button will turn lights And keep them off until pressed again. The lights will remain off until the button IS pressed again, resetting the sensor to Automatic On mode.
Newid Analluogi
Mae'r defnyddiwr yn cael ei atal rhag diffodd y goleuadau trwy'r botwm gwthio.
Modd Rhagfynegol
Pressing the push-button switch turns the lights off and temporarily disables the occupancy detection. After 10 seconds, the occupancy detection reactivates am mmttors for an additional 30 seconds. no «upancyls detected during this period” the sensor will revert to Automatic On operation. If occupancy is detected the sensor will remain in Override Off mode and requires the switch to be pressed in order to restore the sensor to Automatic On.
Predictlve Mode wdth Expiratlon
Pressing push-button switch turns the lights off and temporarily disables the occupancy detection. After 10 s«mds, the occupancy detection reactivates am mmltors for an additional 30 seconds If no occupancy is detected during this period” the gnsor WII/reverts to Automatic On operation.
- Galluogi Switsh
- Newid Analluogi
- Modd Rhagfynegol
- Predictive Mode with Expiration.
5=Darkness Set-Point / Inhibit Set-Point
Y lefel golau amgylchynol lle mae'r synhwyrydd yn gosod y goleuadau i'r gosodiad High Trim.
| Gosodiad | Light Level (fc) | Nodiadau |
|---|---|---|
| 1 | Set NOW* | Default/current setting |
| 2 | 0.1 fc | Very low light |
| 3 | 1 fc | Golau isel |
| 4 | 4 fc | Moderate low light |
| 5 | 8 fc | Golau canolig |
| 6 | 16 fc | Medium-high light |
| 7 | 24 fc* | Default recommended |
| 8 | 32 fc | Golau llachar |
| 9 | 48 fc | Gloyw iawn |
| 10 | 64 fc | Golau uchel |
| 11 | I ffwrdd | Light level off |
| 12 | 96 fc | Maximum standard brightness |
| 13 | 128 fc | Extra bright |
| 14 | 192 fc | Hynod o ddisglair |
| 15 | 256 fc | Gosodiad uchaf |
Set Now will automatically select the Darkness Set-Point based on the current conditions in the room. Lights will go to full bright and sensor will rapidly flash for 15 seconds, allowing the occupant to move out of direct view o synhwyrydd. Unwaith y bydd y dewis pwynt gosod wedi'i gwblhau, bydd y synhwyrydd yn blink dwbl i'w gadarnhau.
7=Photocell Mode
Ataliad yn Unig
Prevents lights from automatically coming on when light level is above the Inhibit Set-Point
- Anabl
- Ataliad yn Unig
9=Restore Defaults
Returns all functions to their original settings.
- Cynnal Cyfredol*
- Adfer Rhagosodiadau
11=LED Operation
Indicates behavior of the device’s LED.
- Arwydd Deiliadaeth*
- Anabl
14 = Llawlyfr Ar Gyfnod Gras
Time period after lights automatically turn off that tho can be reactivated by motion, Applicable only when sensor is in Manual On (Semi Auto) mmie.
- I-Osec
- 3-15see
17 = Amser Gadael Rhagfynegol
Time period after manually switching fights off to leave the space. Applicob/e onbe when sensor in Predictive Off mode.
- I-5s«
- 2-6 eiliad
- 3-7s«
- 4-8 eiliad
- 5-9 eiliad
- 6-10K*
- 7-15K
- 8-20 eiliad
- 9-30K
18 = Amser Gras Rhagfynegol
Time period after Predictive Exit Time fiat sensor rescans the RMRN for remaining occupants. Applicable only when sensor is in Predictive Off mode.
- I-Osec
- 2-5s«
- 3-10K
- 4-20 eiliad
- 5-30see
- 6-40K
- 7-50 eiliad
- 8-60 eiliad
19 = Cyfradd Pylu Ymlaen
Time required for light to reach preset IceL
- 1-0.75 see
- 2-25 eiliad
- 3-5 eiliad
- 4-15s«
20 = Cyfradd pylu
Time required for light to turn Off
- 1-0.75 eiliad
- 2-15see
- 3-5 eiliad
- 4-15 eiliad
CYFARWYDDIADAU GOSOD GWEITHREDOL
PLEASE READ A1 1 7 STEPS BEFORE PROGRAMMING
- Enter programming mode by pressing & holding button until LED flashes rapidly. Release button.
- Enter a specific function by pressing button. The number Of times as the desired function number from the tables on the following pages (e.g., press twice for function 2, Occupancy Time Delay).
- The selected function’s current setting will then be read out in a sequenæ of LED flashes (e.g., five flashes for 10 min). TO change setting, proceed to step 4 before sequence repeats 10 times.
- While the sensor is flashing back current setting, interrupt it by pressing button the number of times for the new desired setting as indicated in the particular function’s detailed table (e.g., press seven times for 15 min). Sensor will begin to flash new setting as confirmation.
- Next, while the sensor is flashing back new setting, interrupt it by pressing and holding button until LED flashes rapidly. Release button.
- As final confirmation and activation Of the new setting, re-enter the function number that was changed (e.g., press twice for function 2, Occupancy Time Delay).
- LED will flash twice indicating acceptance of new setting. If two flashes are not seen, repeat 7 step process

Nodyn:
TO exit programming mode without saving or to change to a different function, wait for the blink back sequence to repeat 10 times, then return to step 1.
GWARANT
Gwarant cyfyngedig 5 mlynedd. Telerau gwarant cyflawn wedi'u lleoli yn www.acuibrands.com/CustomerResourcesTerms_and_conditions.as x
DARLLENWCH A DILYNWCH POB CYFARWYDDIAD DIOGELWCH!
ARBEDWCH Y CYFARWYDDIADAU HYN A DARPARU I'R PERCHENNOG AR ÔL Y GOSOD
- Acuity Brands I One Lithonia Way Conyers, GA 30012
- Ffôn: 800.535.2465 www.acuitybrands.com/sensorswitch @2014-2021 Acuity Brands Lighting, Inc.
- All rights reserved. Rev. 09/27/21 lofl 912-00262-002
Cwestiynau Cyffredin
How do I reset all settings to default?
Navigate to the Restore Defaults option and select 'Restore Defaults' to reset all functions to their original settings.
Dogfennau / Adnoddau
![]() |
sensor switch WSRA Series Wall Switch Sensor with Occupancy [pdfCanllaw Gosod is-wsra 220VAC Edits V5, WSRA Series Wall Switch Sensor with Occupancy, WSRA Series, Wall Switch Sensor with Occupancy, Switch Sensor with Occupancy, Sensor with Occupancy |