1. Rhagymadrodd

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your EARU Electric 3-Phase Auto Transfer Switch (ATS) - 440V 63A. Please read this manual thoroughly before installation and operation to ensure proper functionality and to prevent damage or injury.

The ATS is designed to provide uninterrupted power by automatically transferring loads between phases in a three-phase supply system. It features intelligent monitoring and protection against phase failure, over/under voltage, and overcurrent conditions, ensuring the stability and safety of connected equipment.

2. Gwybodaeth Diogelwch

RHYBUDD: Perygl sioc drydanol. Dim ond personél cymwys ddylai wneud y gosodiad a'r gwasanaethu.

  • Always disconnect power before installing or servicing the ATS.
  • Sicrhewch fod yr holl weirio yn cydymffurfio â chodau trydanol lleol a chenedlaethol.
  • Gwirio cywir cyftage and current ratings before connecting the device.
  • Peidiwch â gweithredu'r ddyfais os yw'n ymddangos ei bod wedi'i difrodi.
  • Keep children away from electrical equipment.

3. Cynnyrch Drosview

The EARU Electric 3-Phase ATS is an intelligent device that continuously monitors your three-phase power supply. It automatically switches single-phase loads to a healthy phase in case of a phase failure or imbalance, ensuring continuous operation of critical equipment.

3.1. Cynnwys Pecyn

  • 1 x EARU Electric 3-Phase Auto Transfer Switch (ATS)

3.2. Front Panel and Indicators

Front panel of EARU Electric 3-Phase ATS with digital display and control buttons

Disgrifiad o'r Delwedd: The front panel of the ATS features a digital display showing voltage for L1, L2, L3 phases and current for L1. Below the display are indicators for Power, Over-voltage (>V), Under-voltage (<V), and Over-current (>I). Control buttons include 'SET' (Menu key), 'Digit+/Up', 'Digit-/Down', and 'Manual ON/OFF' (Power button).

The digital display provides real-time voltage readings for each phase (L1, L2, L3) and the current for L1. Status indicators alert you to the operational state and any detected faults:

  • Pwer: Output indication.
  • >V: Gor-gyfroltage arwydd.
  • <V: Dan-gyfroltage arwydd.
  • > Fi: Over-current indication.

Control buttons allow for parameter settings and manual operation:

  • SET: Menu key for accessing settings.
  • Digit+/Up: Increases value or navigates up in menus.
  • Digit-/Down: Decreases value or navigates down in menus.
  • Llawlyfr YMLAEN / I FFWRDD: Power button for manual control.

4. Gosod a Gosod

The ATS is designed for standard DIN rail mounting. Ensure sufficient space for ventilation and wiring connections.

4.1. Diagram Gwifrau

Wiring diagram for EARU Electric 3-Phase ATS showing input and output connections

Disgrifiad o'r Delwedd: A detailed wiring diagram illustrates the connection points for the ATS. The top terminals are labeled 'IN' with connections for N, L1, L2, L3. The bottom terminals are labeled 'OUT' with connections for N and L1. The diagram shows how to connect the three-phase input to the ATS and how a single-phase load (L1 and N) is connected to the output, with internal connections for phase monitoring and switching.

Follow the wiring diagram carefully. Incorrect wiring can lead to device malfunction or electrical hazards.

  • Connect the incoming three-phase power supply (N, L1, L2, L3) to the 'IN' terminals.
  • Connect the single-phase load (N, L1) to the 'OUT' terminals. The ATS will manage the phase transfer for the L1 output.
  • Ensure all connections are secure and tightened to prevent loose contacts and overheating.

4.2. Troi’r Pŵer Cychwynnol

After completing the wiring, restore power to the system. The ATS will power on and begin monitoring the phases. The digital display will show the current voltage readings for each phase. If all phases are stable and within acceptable limits, the ATS will provide power to the output.

5. Cyfarwyddiadau Gweithredu

The ATS operates automatically, but you can adjust its protection parameters to suit your specific requirements.

5.1. Deall yr Arddangosfa a'r Dangosyddion

The digital display continuously shows the real-time voltage of each phase (L1, L2, L3) and the current on L1. The indicator lights provide quick visual feedback on the device's status and any detected anomalies.

Close-up of EARU Electric 3-Phase ATS digital display showing voltage and current readings

Disgrifiad o'r Delwedd: A close-up view of the ATS digital display. It shows '220V' for L1, L2, and L3, and '63.0A' for L1 current. Below these readings are small indicator icons for Power, >V (Over-voltage), <V (Under-voltage), and >I (Over-current).

5.2. Adjusting Protection Parameters

Use the 'SET' button to enter the parameter setting mode. Use the 'Digit+/Up' and 'Digit-/Down' buttons to navigate through settings and adjust values. Press 'SET' again to confirm and save changes.

Adjustable Protection Parameters
ParamedrYstod GosodGosodiad Diofyn
Over Current Protection Setting Range1-63A/100A30A
Continuous Over Current Protection Times0-20 gwaithODDI AR
Dros Voltage Protection Setting Range230-300V270V
Dros Voltage Protection Recover Setting Range225-295V265V
O dan Voltage Protection Setting Range140-210V170V
O dan Voltage Protection Recover Setting Range145-215V175V
Cyftage & Current Protection Recover Delay1-500s30s

5.3. Automatic Phase Transfer

The ATS automatically monitors the three input phases (L1, L2, L3). If a phase failure or significant voltage imbalance (over/under voltage) is detected on the currently supplying phase, the device will automatically transfer the single-phase output load to a healthy, stable phase within the same supply. This process is designed to be seamless and rapid, minimizing power interruption to connected equipment.

5.4. Automatic Recovery

Once the primary phase recovers and stabilizes, the ATS will intelligently switch the load back to the primary source, ensuring optimal power distribution and preventing equipment damage from unstable power. The recovery delay can be configured as per your operational needs.

6. cynnal

The EARU Electric ATS is designed for minimal maintenance. However, periodic checks are recommended to ensure optimal performance and longevity.

  • Glanhau: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Gwiriadau Cysylltiad: Archwiliwch yr holl gysylltiadau gwifrau o bryd i'w gilydd i sicrhau eu bod yn parhau i fod yn dynn ac yn rhydd rhag cyrydiad.
  • Amodau Amgylcheddol: Sicrhewch fod yr amgylchedd gweithredu yn aros o fewn yr ystodau tymheredd a lleithder penodedig.

7. Datrys Problemau

If you encounter issues with your ATS, refer to the following common problems and solutions:

Canllaw Datrys Problemau
ProblemAchos PosiblAteb
Dim allbwn pŵerNo input power; all phases unstable; device in fault state.Check incoming power supply. Verify all phases are stable. Check fault indicators.
">V" or "<V" indicator litGor-gyfroltage neu dan-cyftage detected on a phase.Gwirio mewnbwn cyftage stability. The ATS will automatically transfer if another phase is healthy.
">I" indicator litOver-current detected on the output.Reduce load on the output. Check for short circuits in the connected equipment.
Device not transferring phasesNo healthy alternative phase available; transfer delay setting too long.Ensure at least one healthy phase is present. Check and adjust the transfer delay settings.
Arddangosfa ddigidol ddim yn gweithioNo power to the device; internal fault.Check power supply. If power is present and display is off, contact support.

For issues not covered here, please contact EARU customer support.

8. manylebau

Detailed specifications and dimensions of EARU Electric 3-Phase ATS

Disgrifiad o'r Delwedd: This image displays the physical dimensions of the ATS (90mm width, 96mm height, 66mm depth) and a table of detailed technical specifications, including current rating, voltage, frequency, and various protection setting ranges.

NodweddManylyn
BrandEARU
Rhif ModelEARU-1012
Modd GweithreduAR-OFF
Graddfa Gyfredol63 Amps
Vol Gweithredutage440 Volts (AC 3*220V (N-L1/L2/L3))
Amlder â Gradd50/60Hz
Math CyswlltAr agor fel arfer
Math o GysylltyddStandard DIN rail 63A
Math Cylchdaith4-ffordd
Deunydd CyswlltCopr
Over Current Protection Setting Range1-63A/100A (Default 30A)
Continuous Over Current Protection Times0-20 Times (Default OFF)
Dros Voltage Protection Setting Range230-300V (Default 270V)
Dros Voltage Protection Recover Setting Range225-295V (Default 265V)
O dan Voltage Protection Setting Range140-210V (Default 170V)
O dan Voltage Protection Recover Setting Range145-215V (Default 175V)
Cyftage & Current Protection Recover Delay1-500s (Default 30s)
Pwysau Eitem450 g
Dimensiynau Pecyn15 x 15 x 15 cm
Gwlad TarddiadIndia

9. Gwarant a Chefnogaeth

9.1. Gwybodaeth Gwarant

The EARU Electric 3-Phase Auto Transfer Switch (ATS) comes with a Gwarant Gwneuthurwr 1 Flwyddyn o ddyddiad y pryniant. Mae'r warant hon yn cwmpasu diffygion mewn deunyddiau a chrefftwaith o dan ddefnydd arferol. Nid yw'n cwmpasu difrod a achosir gan osod amhriodol, camddefnydd, damweiniau, neu addasiadau heb awdurdod.

9.2. Cefnogaeth i Gwsmeriaid

For technical assistance, warranty claims, or any questions regarding your EARU Electric ATS, please contact your retailer or the manufacturer directly. Ensure you have your product model number (EARU-1012) and proof of purchase available when contacting support.

© 2023 EARU Electric. All rights reserved.