VEICHI AC10 Series (specifically AC10-T/S2-1R5G-B-220V and compatible variants)

VEICHI AC10 Series Frequency Converter User Manual

Model: AC10-T/S2-1R5G-B-220V and Compatible Variants

1. Rhagymadrodd

This manual provides essential information for the safe and efficient installation, operation, and maintenance of the VEICHI AC10 series frequency converters. Please read this manual thoroughly before using the product to ensure proper handling and to prevent damage or injury.

The VEICHI AC10 series frequency converters are designed for general-purpose applications, offering reliable motor control and energy efficiency. This manual covers models such as AC10-T/S2-R75G-B-220V, AC10-T/S2-1R5G-B-220V, AC10-T/S2-2R2G-B-220V, AC10-T3-R75G-B-380V, and AC10-T3-1R5G-B-380V.

2. Rhagofalon Diogelwch

Always observe the following safety precautions to prevent electric shock, fire, or personal injury. Failure to comply may result in severe consequences.

  • Personél Cymwys: Installation, wiring, operation, and maintenance must be performed by qualified electrical personnel only.
  • Datgysylltu Pŵer: Always disconnect all power sources before performing any wiring or maintenance. Wait at least 5 minutes after power off for the capacitor discharge indicator to extinguish.
  • Sylfaen: Ensure the frequency converter is properly grounded according to local electrical codes.
  • Amodau Amgylcheddol: Do not operate the converter in environments exceeding specified temperature, humidity, or dust levels.
  • Gorchuddion Amddiffynnol: Do not remove protective covers or touch internal components while power is applied.

3. Cynnyrch Drosview

The VEICHI AC10 series frequency converter features a compact design with an integrated control panel for easy operation and monitoring.

Blaen view of the VEICHI AC10 series frequency converter, showing the digital display, control buttons (PRG, UP, DOWN, RUN, STOP/RESET, SET/SHIFT), and terminal blocks.

Ffigur 3.1: Blaen view of the VEICHI AC10 Frequency Converter. This image displays the main unit, highlighting the digital display for parameters, control buttons for programming and operation, and the various terminal blocks for power and control wiring. A screwdriver is visible in the side compartment.

3.1. Control Panel Layout

The control panel consists of a digital display and several function buttons:

  • Arddangos: Shows operational parameters, fault codes, and programming values.
  • PRG (Rhaglen): Yn mynd i mewn/gadael y modd gosod paramedr.
  • Saethau I FYNY/I LAWR: Navigate through parameters, adjust values.
  • RHEDEG: Yn cychwyn y modur.
  • STOPIO/AILOSOD: Stops the motor, resets fault conditions.
  • SET/SHIFT: Confirms parameter settings, shifts cursor during input.

4. Gosod a Gosod

4.1. Mowntio

Mount the frequency converter vertically on a flat, non-flammable surface. Ensure adequate ventilation space around the unit (at least 10 cm above and below, 5 cm on sides) for heat dissipation.

4.2. Gwifrau

Refer to the wiring diagram provided with your specific model for detailed connections. General wiring guidelines:

  • Power Input (R, S, T or L1, L2): Connect to the main power supply. Ensure correct voltage (220V or 380V depending on model).
  • Allbwn Modur (U, V, W): Connect to the motor terminals.
  • Tir (PE): Connect to a reliable ground point.
  • Terfynellau Rheoli: For external control signals (e.g., start/stop, speed reference, fault output).

Warning: Incorrect wiring can lead to severe damage to the unit or personal injury. Consult a qualified electrician if unsure.

5. Cyfarwyddiadau Gweithredu

5.1. Troi’r Pŵer Cychwynnol

  1. After completing all wiring, apply power to the frequency converter.
  2. The display will light up, typically showing "0.00" or a default frequency.

5.2. Basic Operation (Keypad Control)

  1. Amlder Gosod: Gwasgwch y PRG button to enter parameter mode. Navigate to the frequency setting parameter (e.g., F0.01) using the I FYNY/I LAWR saethau. Gwasgwch SET/SHIFT to edit, adjust value, then SET/SHIFT eto i gadarnhau. Pwyswch PRG i ymadael.
  2. Cychwyn Modur: Gwasgwch y RHEDEG button. The motor will accelerate to the set frequency.
  3. Stopio Modur: Gwasgwch y STOP / AILOSOD button. The motor will decelerate and stop.

5.3. Gosodiadau Paramedr

The AC10 series has a comprehensive set of parameters for various functions. Refer to the detailed parameter list in the full product manual for advanced configurations (e.g., acceleration/deceleration times, motor parameters, control modes).

Exampparamedrau gyda:

  • F0.00: Run command source (keypad, terminal, communication)
  • F0.01: Frequency setting source (keypad, analog input, communication)
  • F0.03: Amlder allbwn mwyaf
  • F0.04: Amser cyflymu
  • F0.05: Amser arafu

6. cynnal

Regular maintenance ensures the longevity and reliable operation of your frequency converter.

  • Glanhau: Periodically clean the cooling fins and fan to prevent dust accumulation, which can hinder heat dissipation. Use compressed air or a soft brush. Ensure power is off before cleaning.
  • Gwiriad Terfynell: Annually check all wiring terminals for tightness. Loose connections can cause overheating or intermittent operation.
  • Gwiriad Amgylcheddol: Gwiriwch fod yr amgylchedd gweithredu yn aros o fewn yr ystodau tymheredd a lleithder penodedig.
  • Fan Replacement: Cooling fans have a limited lifespan. Consider replacing them every 3-5 years, depending on operating conditions, to maintain optimal cooling.

7. Datrys Problemau

This section provides common issues and their potential solutions. For complex problems, contact technical support.

Problem/Fault CodeAchos PosiblAteb
No Display/PowerDim pŵer mewnbwn; Ffiws wedi chwythu; Nam mewnol.Check power supply; Check fuses; Contact support.
Overcurrent (OC) FaultMotor overload; Short circuit in motor wiring; Rapid acceleration/deceleration.Check motor load; Inspect motor wiring; Increase acceleration/deceleration time.
Overvoltage (OV) FaultMewnbwn cyftage too high; Rapid deceleration with high inertia load.Gwirio mewnbwn cyftage; Increase deceleration time; Consider braking resistor.
Danddaeartage (UV) FaultMewnbwn cyftage too low; Power supply dip.Gwirio mewnbwn cyftage; Ensure stable power supply.
Overheat (OH) FaultAmbient temperature too high; Fan failure; Blocked ventilation.Improve ventilation; Clean cooling fins; Check fan operation.

To reset a fault, press the STOP / AILOSOD button after resolving the cause.

8. manylebau

The following specifications are typical for the VEICHI AC10 series. Specific values may vary slightly by model.

ParamedrGwerth/Amrediad
Mewnbwn VoltageSingle-phase 220V (AC10-T/S2 models) or Three-phase 380V (AC10-T3 models)
Allbwn Ystod Amlder0.00 Hz - 400.00 Hz
Modd RheoliV/F control, Sensorless vector control
Gallu Gorlwytho150% of rated current for 60 seconds
Nodweddion GwarchodOvercurrent, Overvoltage, Undervoltage, Overheat, Overload, Short circuit
Tymheredd Gweithredu-10°C i 40°C (14°F i 104°F)
LleithderLess than 90% RH (non-condensing)
Dimensiynau (tua)Varies by power rating (e.g., 2 x 2 x 2 inches for smaller models)
Pwysau (tua)Varies by power rating (e.g., 4.41 Pounds for smaller models)

Note: For precise specifications of your specific model, refer to the product label or the comprehensive technical datasheet.

9. Gwarant a Chefnogaeth

9.1. Gwybodaeth Gwarant

This product is typically covered by a manufacturer's warranty against defects in materials and workmanship for a period specified at the time of purchase. Please retain your proof of purchase for warranty claims. The warranty does not cover damage caused by improper installation, misuse, unauthorized modification, or operation outside of specified environmental conditions.

For specific warranty terms and conditions, please refer to the documentation provided with your purchase or contact the seller.

9.2. Cymorth Technegol

If you encounter issues that cannot be resolved using the troubleshooting guide, or require further technical assistance, please contact your supplier or the manufacturer's authorized service center.

When contacting support, please be prepared to provide the following information:

  • Product Model Number (e.g., AC10-T/S2-1R5G-B-220V)
  • Serial Number (if applicable)
  • Dyddiad Prynu
  • Detailed description of the problem, including any fault codes displayed.

© 2025 VEICHI. All rights reserved.

Gall y llawlyfr hwn newid heb rybudd.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.