SJE Rhombus 1005481

SJE-Rhombus Tank Alert XT Indoor/Outdoor Tank Alarm User Manual

Model: 1005481 | Brand: SJE Rhombus

1. Rhagymadrodd

The SJE-Rhombus Tank Alert XT is an advanced indoor/outdoor alarm system designed to provide crucial audio and visual warnings for threatening liquid level conditions. This system is ideal for various applications including lift pump chambers, sump pump basins, holding tanks, sewage systems, agricultural uses, and other non-potable water environments. Its robust design ensures reliable operation and automatic reset functionality once the alarm condition is resolved.

SJE-Rhombus Tank Alert XT alarm unit and float switch

Ffigur 1: The SJE-Rhombus Tank Alert XT system components. This image displays the gray alarm unit with a red beacon on top, a black float switch with its coiled cable, and a metal hose clamp along with two screws for mounting. The alarm unit features a "TANK ALERT XT" label, SJE-Rhombus logo, and a power/silence switch.

2. Nodweddion Allweddol

  • Amgaead Sy'n Ddiogelu'r Tywydd: The alarm enclosure meets Type 3R water-tight standard, ensuring durability for indoor/outdoor use.
  • Automatic Alarm Reset: The system automatically resets once the liquid level condition returns to normal.
  • Horn Silence Switch: Allows the user to silence the audible alarm while the visual beacon remains active until the condition is resolved.
  • Alarm Test Switch: Provides a convenient way to test the alarm's functionality.
  • High Decibel Alarm Horn: Sounds at 85 decibels at 3 meters (10 feet) to ensure clear notification.
  • Gweithrediad Annibynnol: When installed on a separate circuit, the alarm system operates even if the pump circuit experiences a failure.

3. manylebau

ManylebManylyn
Cyftage120 VAC, 50/60 Hz, 7 wat ar y mwyaf. (cyflwr larwm)
Alarm Enclosure Dimensions16.51 x 11.43 x 7.62 cm (6.5 x 4.5 x 3.0 modfedd)
Math o AmgaeadIndoor/outdoor weatherproof thermoplastic, meets Type 3R water-tight standard
Horn Larwm85 decibels at 3 meters (10 feet), meets Type 3R water-tight standard
Alarm BeaconMeets Type 3R water-tight standard
Prawf/Switsh TawelwchCertified to IP66 and IP68 standards
Float Switch Cable Length4.57 meters (15 feet), flexible 18 gauge, 2 conductor (UL) SJOW
Deunydd arnofioHigh impact, corrosion resistant PVC housing
Float Operating TemperatureHyd at 60°C (140°F)
Math o switsh arnofioHermetically sealed steel capsule with mercury-to-mercury contacts
Math MowntioWal Mount
Pwysau Eitem2.99 pwys
Dimensiynau Cynnyrch6.5 x 3 x 4.5 modfedd

4. Gosod a Gosod

Proper installation is crucial for the reliable operation of your Tank Alert XT system. It is recommended that installation be performed by a qualified electrician or technician in accordance with local electrical codes.

4.1. Cydrannau Drosview

  • Amgaead Larwm: Houses the alarm circuitry, horn, beacon, and control switches.
  • Newid arnofio: A liquid level sensor that activates the alarm when a predetermined level is reached.
  • Caledwedd Mowntio: Includes a hose clamp and screws for securing the float switch and alarm unit.

4.2. Camau Gosod

  1. Dewis Lleoliad: Choose a suitable indoor or outdoor location for the alarm enclosure. Ensure it is easily accessible for testing and silencing, and within reach of a 120 VAC power source. The enclosure is designed for wall mounting.
  2. Mount Alarm Enclosure: Securely mount the alarm enclosure to a flat surface using appropriate fasteners. Ensure it is level and stable.
  3. Install Float Switch:
    • Determine the desired alarm activation level within the tank or basin. The float switch should be positioned so it activates when the liquid reaches this critical level.
    • Defnyddiwch y cl. mowntio a ddarperiramp to secure the float switch cable to the discharge pipe or a suitable mounting point inside the tank. Ensure the float can move freely up and down without obstruction.
    • Route the float switch cable back to the alarm enclosure, protecting it from damage.
  4. Cysylltiadau Gwifren:
    • RHYBUDD: Ensure power is disconnected before making any electrical connections.
    • Connect the float switch wires to the designated terminals inside the alarm enclosure as per the wiring diagram provided with the product packaging.
    • Connect the alarm unit to a dedicated 120 VAC power supply. For optimal safety and independent operation, it is recommended to connect the alarm to a separate circuit from the pump.
  5. System Prawf: Once all connections are secure and power is restored, perform a system test. Manually raise the float switch to simulate a high liquid level. The alarm horn should sound, and the red beacon should activate. Use the silence switch to confirm it silences the horn, and then lower the float to confirm auto-reset.

5. Cyfarwyddiadau Gweithredu

The Tank Alert XT system is designed for straightforward operation, providing clear indications of liquid level conditions.

5.1. Actifadu Larwm

When the liquid level in the tank or basin rises to the point where it activates the float switch, the alarm system will trigger:

  • The audible alarm horn will sound at 85 decibels.
  • The red alarm beacon on top of the enclosure will illuminate.

5.2. Tawelu'r Larwm

To silence the audible horn, press the Tawelwch switch located on the front of the alarm enclosure. The horn will cease, but the red alarm beacon will remain illuminated. This visual indicator will stay on until the liquid level returns to normal, signifying that the condition has been remedied.

5.3. Automatic Reset

Once the liquid level drops below the float switch activation point, the system will automatically reset. The red alarm beacon will turn off, and the system will be ready to detect future high-level conditions.

5.4. Profi'r Larwm

It is recommended to periodically test the alarm system to ensure proper functionality. Press the PRAWF switch on the front of the enclosure. This will simulate an alarm condition, activating both the horn and the beacon. Release the switch to return to normal operation.

6. cynnal

Regular maintenance helps ensure the longevity and reliability of your Tank Alert XT system.

  • Profi Cyfnodol: Test the alarm system monthly using the TEST switch to confirm both audible and visual indicators are working.
  • Float Switch Inspection: Periodically inspect the float switch and its cable for any signs of wear, damage, or buildup that might impede its free movement. Clean the float switch if necessary, especially in applications with viscous liquids or debris.
  • Enclosure Check: Ensure the alarm enclosure is free from dirt, moisture, and insect intrusion. Keep the ventilation openings clear if present.
  • Uniondeb Cebl: Check all wiring and cables for secure connections and absence of damage.
  • Cyflenwad Pŵer: Verify that the alarm unit is continuously receiving power.

Nodyn: Always disconnect power to the alarm unit before performing any maintenance or inspection inside the enclosure.

7. Datrys Problemau

If your Tank Alert XT system is not functioning as expected, refer to the following common issues and solutions:

ProblemAchos PosiblAteb
Alarm not sounding/beacon not lighting up during high level or test.Dim pŵer i'r uned.
Switsh arnofio diffygiol.
Cysylltiad gwifrau rhydd.
Damaged alarm unit.
Gwiriwch y cyflenwad pŵer a'r torrwr cylched.
Verify float switch operation by manually raising it.
Inspect all wiring connections inside the enclosure.
Contact SJE-Rhombus support if unit is damaged.
Mae larwm yn swnio'n barhaus.Liquid level remains high.
Float switch stuck in activated position.
Faulty float switch or wiring.
Address the high liquid level condition.
Inspect float switch for obstructions or debris; clean if necessary.
Check float switch and wiring for damage.
Alarm horn silenced, but beacon remains off.Faulty alarm beacon.
Problem gwifrau mewnol.
Contact SJE-Rhombus support for repair or replacement.
Alarm does not auto-reset.Liquid level still high.
Float switch stuck or damaged.
Ensure liquid level has dropped below activation point.
Inspect and clean float switch; ensure free movement. Replace if damaged.

If troubleshooting steps do not resolve the issue, please contact SJE-Rhombus customer support.

8. Gwarant a Chefnogaeth

SJE-Rhombus products are manufactured to high standards and are typically backed by a manufacturer's warranty. Specific warranty terms and conditions, including duration and coverage, are usually provided with the product packaging or can be found on the official SJE-Rhombus websafle.

For technical assistance, warranty claims, or to purchase replacement parts, please contact SJE-Rhombus customer support directly. Have your product model number (1005481) and date of purchase available when contacting support.

SJE-Rhombus Official Websafle: www.sjerhombus.com

Please note that product specifications and features are subject to change without notice. Always refer to the latest documentation provided by the manufacturer.

© 2024 SJE Rhombus. All rights reserved.

This manual is for informational purposes only. SJE Rhombus assumes no responsibility for errors or omissions.